The WSC11 is intended for use in building automation. It records the following measured variables:
The interface to the device is digital and consists of an RS485 interface. Together with the ID-based communication, the interface enables the operation of the weather station in a bus.
The device has a GPS receiver. This is used for position and time determination, from which the position of the sun is also calculated.
The following parameters can be measured:
wind velocity
wind direction
Brightness (North, East, South, West)
twilight
global radiation
precipitation
temperature
relative humidity
air pressure
Time / Date
Geostationary data
degree of longitude
latitude
sun's position
elevation
azimuth
Application: | Building automation, Cleanroom and process measurement technology, Disposal site monitoring, Environmental Engineering, Environmental Protection, Evaporation, industry, Site supervision, Solar technology, Transport monitoring, Ventilation and air conditioning |
Parameter: | air pressure, Air pressure QFH, Air pressure QFN, air temperature, Dämmerung, Globalstrahlung, Helligkeit, Position, Precipitation, Relative humidity, Sunshine duration, UV-Strahlung, Windgeschwindigkeit, Windrichtung |
Manufacturer: | Thies Clima |
Norm - WMO: | WMO-No,8 7th Edition Part I Chapter 2 Measurement of temperature, WMO-No,8 7th Edition Part I Chapter 3 Measurement of atmospheric pressure, WMO-No,8 7th Edition Part I Chapter 4 Measurement of humidity, WMO-No,8 7th Edition Part I Chapter 5 Measurement of surface wind, WMO-No,8 7th Edition Part I Chapter 7 Measurement of radiation, WMO-No,8 7th Edition Part I Chapter 7 Measurement of radiation, WMO-No,8 7th Edition Part I Chapter 8 Measurement of sunshine duration, WMO-No,8 7th Edition Part II Chapter 1 Measurements at automatic weather stations, WMO-No,8 7th Edition Part II Chapter 9 Radar measurements, WMO-No,8 7th Edition Part II Chapter 11 Urban observations, WMO-No,8 7th Edition Part II Chapter 12 Road Meteorological Measurements, WMO No, 8 7th Edition Part 1 Chapter 6 of precipitation |
Norm: | VDE 0839-81-1: 1993-03. Electromagnetic compatibility (EMC)., VDE 0875-11: 2011-04 Industrial, scientific and medical equipment - Radio disturbance characteristics - Limits and methods of measurement, VDI 3786 13 Meteorological measurements - measuring station, VDI 3786 Paget 2 Wind., VDI 3786 Part 3 air temperature, VDI 3786 Part 4 humidity, VDI 3786 Part 5 Radiation Measurement, VDI 3786 Part 7 of precipitation, VDI 3786 Part 16 measuring the air pressure |
atmospheric air pressure measurement method: | MEMS kapazitiv |
atmospheric air pressure measurement accuracy [hPa]: | ±0,5 hPa (bei Raumtemp. 25 °C) |
atmospheric air pressure measuring range [hPa]: | 300 – 1100 mbar |
Humidity measurement method: | Capacitives Polymer |
Humidity measuring range [% RH]: | 0 ... 100 % r.F. |
Humidity measuring accuracy [% R.H.]: | ±5% (bei 20 °C und <80 % r.F.) |
Air temperature measuring range [° C]: | -40 bis +60°C |
Air temperature measurement accuracy [K]: | ±1,0 °C (+5 ... +60 °C), sonst < ±2,0 °C |
Wind speed measurement methods: | thermoelektrisch |
Wind speed threshold [m/s}: | 0,5 m/s |
Wind speed measurement accuracy [m / s]: | ±1 m/s bzw. 5 %, der größere Wert gilt Als Pdf herunterladen |
Wind speed measuring range [m / s]: | 0 ... 40 m/s |
Wind Direction Measurement process: | thermoelektrisch |
Windrichtung Ansprechschwelle [°]: | < 0,5 m/sec |
Wind direction accuracy [°]: | ± 10 ° |
Windrichtung Messbereich: | 0 - 360° |
Global radiation measuring range [m/m2]: | , 0...1300W/m2 |
Global radiation measuring accuracy [W{m2]: | 10% oder ±120 W/m², größerer Wert gilt Sonnenstand |
Global radiation spectrum [nm]: | 300...1100 nm |
Globalstrahlungsmessverfahren: | Silizium-Pyranometer |
Sonnenstandmessverfahren: | Berechnet |
Dämmerungsmessbereich:: | , 0...999 Lux |
Dämmerungsmessgenauigkeit: | ±10 lx |
Precipitation type: | Regen, Schnee, Schneeregen, Eisregen, Hagel |
Niederschlagsstatus: | 1/0 (ja/ Nein) |
Dimension (cm): | 227 x 145 x 130 mm |
Power consumption: | 120 mA (bei Windstille @24V); 360 mA (ab ca. 7m/s Wind @24V) |
voltage supply: | 4...32 VDC |
Degree of protection: | IP67 |
Heating: | 1,1W |
Interfaces: | MODBUS RTU, Rs485, UMB, UMB ASCII 2.0, WLAN |
Housing: | Plastic |
Weight (Kg): | 0,5 |